Distribution Transformer Manufacturer Contact Number

03-07 2025 | By:

Types and Model Designations of Distribution Transformers
Distribution transformers are critical components in power systems, designed to step down voltage for end-users. Their model designations reflect technical specifications and structural features, standardized globally for clarity. Here’s an overview of key aspects:

1. Model Structure

Distribution transformer models are coded using letters and numbers to indicate characteristics :

  • Phase Configuration:
    • Single-phase: Marked as “D” (e.g., D10).
    • Three-phase: Marked as “S” (e.g., S11).
  • Cooling Method:
    • Oil-immersed: No letter (default) or “J” for forced oil circulation.
    • Dry-type: Marked as “G” (air-cooled) or “C” (resin-encapsulated).
  • Winding Material:
    • Copper windings are default (no code), while aluminum is marked as “L”.
  • Voltage Class:
    • Rated high-voltage side (e.g., 10kV or 35kV) follows the capacity value.

A typical model, like S11-M-630/10, deciphers as:

  • S: Three-phase
  • 11: Design series (energy-efficient)
  • M: Sealed tank
  • 630: Capacity (kVA)
  • 10: High-voltage rating (kV)

2. Common Types and Applications

  • Oil-immersed Transformers:
    Widely used for outdoor installations due to robust cooling (e.g., S9, S11). Ideal for rural grids and industrial zones .
  • Dry-type Transformers:
    Fire-resistant and eco-friendly (e.g., SCB10). Suited for buildings, hospitals, and metro systems .
  • Amorphous Core Transformers:
    Marked as “SH15”, reducing no-load losses by 70-80% compared to traditional models, perfect for low-load scenarios .

3. Technical Parameters

Key parameters include:

  • Capacity: Ranges from 50 kVA (small buildings) to 6300 kVA (urban substations).
  • Insulation Class: “F” (155°C) or “H” (180°C) for high-temperature resilience.
  • Impedance Voltage: Typically 4-6% to limit short-circuit currents .

4. Evolution and Standards

Modern standards prioritize energy efficiency. For example, S13 series reduces no-load loss by 25% over S11 . International codes like IEC 60076 align with Chinese GB standards for global compatibility.

In summary, distribution transformer models encapsulate critical engineering choices, balancing efficiency, safety, and environmental adaptability. Understanding these codes aids in selecting optimal units for diverse grid demands.

Performance Parameters

Rated capacity (kVA) Voltagegroup Vectorgroup Loss (W) No-load current(%) Impedance voltage(%) Boundary dimension (L×W×H,mm) Weight (kg)
HV(kV) LV(kV) No-loadloss(W) Loadloss(W)
30 20 22 24 0.4 Dyn11 or Yyn0 100 690/660 2.1 5.5 670×310×615 346
50 130 1010/960 2.0 700×325×630 417
80 180 1440/1370 1.8 755×355×690 556
100 200 1730/1650 1.6 785×360×685 619
125 240 2080/1980 1.5 805×370×720 703
160 290 2540/2420 1.4 850×385×735 794
200 340 3000/2860 1.3 865×405×805 935
250 400 3520/3350 1.2 905×415×935 1086
315 480 4210/4010 1.1 925×440×915 1226
400 570 4970/4730 1.0 970×465×960 1468
500 680 5940/5660 1.0 1035×500×1010 1758
630 810 6820 0.9 6.0 1110×525×1075 2074
800 980 8250 0.8 1190×580×1155 2840
1000 1150 11330 0.7 1205×560×1195 2842
1250 1380 13200 0.7 1185×590×1205 3168
1600 1660 15950 0.6 1225×565×1345 3800
2000 1950 19140 0.6 1310×615×1435 4633
2500 2340 22220 0.5 1390×660×1510 5329

Rated capacity (kVA) Voltagegroup Vectorgroup Loss (W) No-load current (%) Impedance voltage (%) Boundan dimension (L×W×H,mm) Weight (kg)
HV (kV) LV(kV) No-loadloss(W) Loadloss(W)
30 11 10.5 10 6 0.4 Dyn11 or Yyn0 100 630/600 1.5 4 670×310×615 346
50 130 910/870 1.3 700×325×630 417
80 180 1310/1250 1.2 755×355×690 556
100 200 1580/1500 1.1 785×360×685 619
125 240 1890/1800 1.1 805×370×720 703
160 280 2310/2200 1.0 850×385×735 794
200 340 2730/2600 1.0 865×405×805 935
250 400 3200/3050 0.9 905×415×935 1086
315 480 3830/3650 0.9 925×440×915 1226
400 570 4520/4300 0.8 970×465×960 1468
500 680 5410/5150 0.8 1035×500×1010 1758
630 810 6200 0.6 4.5 1110×525×1075 2074
800 980 7500 0.6 1190×580×1155 2840
1000 1150 10300 0.6 1205×560×1195 2842
1250 1360 12000 0.5 1185×590×1205 3168
1600 1640 14500 0.5 1225×565×1345 3800
2000 1940 18300 0.4 5.0 1310×615×1435 4633
2500 2290 21200 0.4 1390×660×1510 5329